THEATRE DESIGN AND VENTILATION

Понравилась презентация – покажи это...





Слайд 0

THEATRE DESIGN AND VENTILATION DR.LOKESH SHAROFF Orthopaedic surgeon, Mumbai, India


Слайд 1

CONCEPT It was first introduced by SIR JOHN CHARNLEY


Слайд 2

ZONES IN THEATRE OUTER ZONE – rest of the hospital outside the theatre complex CLEAN ZONE – theatre complex outside the operating area ASEPTIC ZONE – Operating area DISPOSAL ZONE – Separate exit for contaminated / used linen and instruments


Слайд 3

REQUIREMENTS AIR DELIVERY SYSTEM AIR FILTERATION SYSTEM TEMPERATURE CONTROL HUMIDITY CONTROL


Слайд 4

TEMPERATURE CONTROL - Ideal working temperature is 19-20 * C – to minimize perspiration - But causes pt. hypothermia - PT. body temp. should be 24-26 * C TO AVOID HYPOTHERMIA


Слайд 5

HUMIDITY CONTROL - Should be around 40-60% - Fastest death of organisms occur at 50% humidity


Слайд 6

AIRBORNE PARTICLES - Measured as BCP/MM3 – Bacteria carrying particles OR CFU/MM3 – Colony forming units - Each person emits 10k cfu/min at rest and 50k cfu/min with activity - This is reduced in SCRUBS to 140-830 cfu/min with fask mask and caps.


Слайд 7

AIRBORNE PARTICLES - CONVENTIONAL AC (well maintained)- gives 50-500 cfu/mm3 - All particles are not viable – viable : non viable ratio is 1:1000 - Smallest particle in theatre seen in bright light is 12 microns - Smallest particle that can carry bacteria is 4-5 microns


Слайд 8

AIR FILTERS- 4 LEVELS ROUGHING FILTERS removes Large particles and also protects sensitive final filters PREFILTERS should be 95% efficient FINAL FILTERS should be 95% efficient with a particle size of 3 microns HEPA FILTERS should be 99.97% efficient with a particle size of 0.3 microns


Слайд 9

HEPA FILTERS - Each hepa filter has a manometer attached to it to measure the amount of resistance to filteration for clogging purposes.


Слайд 10

TYPES OF VENTILATION High velocity air flow - high speed jets towards operating table - high speed air at periphery Laminar air flow - horizontal - vertical


Слайд 11

CONVENTIONAL WALL DIFFUSER


Слайд 12

- Produces plenum - No control of air over operating area - Upto 500 bcp/mm3 – not acceptable for operation theatres


Слайд 13

HIGH VELOCITY AIR JET


Слайд 14

- Jets increase air turbulence - Flow at 0.6 m/s - Jets may not point at right place and may dessicate the wound


Слайд 15

Vertical laminar flow - Room within a room principle - Air is passed through hepa filters from ceiling downwards - Flow at 0.3 m/s - entrainment can happen by moving personnel


Слайд 16

Horizontal laminar flow - Forms part of a wall - Easy to install - Movement across it will cause uncontrollable turbulence - adequate clean zone is not possible


Слайд 17

PERIPHERAL LAMINAR


Слайд 18

CONVENTIONAL LAMINAR


Слайд 19

Vertical laminar with canopy and side panels - Canopy – to overcome peripheral entrainment - side panels – extend down to floor to within 20cms from floor - very successful – 10 bcp/m3


Слайд 20

Without side panels


Слайд 21

- Peripheral entrainment air 0.6 m/s - Higher energy consumption - movement causes deflection of contaminants


Слайд 22

EXPONENTIAL AIR FLOW


Слайд 23

- Trumpet shaped air flow - Downward and radially outward flow of air - fliteration down to 1 micron - Trays can be positioned even upto ? m outside the actual canopy


Слайд 24

STANDARDS IN AIR FLOW - Direction of air flow shall be under positive control - max. viable organisms should be not more than 1 cfu/mm3 - ULTRA CLEAN ZONE – is less than 10 cfu/mm3


Слайд 25

AIR CHANGES ATLEAST 20-40 AIR CHANGES PER HOUR Pressure gradient should be 1.3-2.5mm h2O (more pressure causes rapid drying of the wound)


Слайд 26

AIR QUALITY CONTROL - Done by CASTELLA SLIT SAMPLER


Слайд 27

WATER SUPPLY IN OT - Tanks and pipes – regular inspection for leakages - Bore well water should be avoided as far as possible - tanks and containers should have covers/lids to protect from dust - water sterilised by ultraviolet radiation


Слайд 28

ANTIBIOTIC PROPHYLAXIS - CHOICE OF AGENT Active against comon pathogens Take into account drug allergy and sensitivity cefazolin/cefotaxim preferred-long duration clinda/vanco in penicillin allergy pts. Modification for pre-existing cultures if already on abx – then continue same


Слайд 29

ANTIBIOTIC PROPHYLAXIS TIMING Within 15-60 mins prior to incision Vanco should be given 2 hrs before Infusion should complete before incision


Слайд 30

ANTIBIOTIC PROPHYLAXIS - DURATION Further dose efficacy is doubtful Max 24 hrs if only prophylatic intra-op – repeat if length of sx more than half life of drug repeat dose if blood loss >1500ml not to continue abx till drain removal


Слайд 31

ANTIBIOTIC PROPHYLAXIS - RISKS - PENICILLIN ALLERGY - ANAPHYLAXIS - ABX ASSOCIATED DIARRHOEA - CLOSTRIDIUM DIFFICLE INFECTION - ABX RESISTANCE - MULTI-RESISTANCE CARRIAGE – SCREENING SHOULD BE DONE IN HIGH RISK CASES


Слайд 32

THANK YOU *Pictures taken from journal of orthopedics today


×